RiLine60 connection system Busbar systems Page 261 Component adaptors Page 269 Fuse elements Page 280 Material: Cover: 3439.010 Technical information: Chassis: − ABS When connecting round Available at www.rittal-corp.com − Polyamide (PA 6.6). − Fire protection corresponding conductors 300 mm2 with ring − Fire protection corresponding to to UL 94-V0 terminals, the terminal clamps Detailed drawings: UL 94-V0 fitted as standard in the busbar Available at www.rittal-corp.com Color: connection adaptors must be Chassis RAL 7035 replaced with screws and/or bolts 3439.010: M10. − Fiberglass-reinforced, Note: thermoplastic polyester (PBT) The technical data given in − Fire protection corresponding to the tables may vary for UL UL 94-V0 applications. Busbar connection adaptor 125 A/250 A/800 A, cable outlet top/bottom Design Packs Of 3-pole 4-pole Page Rated current up to 125 A 250 A 800 A 125 A 250 A Rated operating voltage 690 V~ 690 V~ 690 V~ 690 V~ 690 V~ Cable outlet top/bottom Connection of round conductors mm2 • fine-wire with wire end ferrule 10 – 25 35 – 120 95 – 185 10 – 25 35 – 120 • multi-wire 16 – 35 35 – 120 95 – 300 16 – 35 35 – 120 • solid – – – – – Clamping area for laminated copper bars W x H mm 10 x 7.8 18.5 x 15.5 33 x 20 10 x 7.8 18.5 x 15.5 Width mm 55 90 129 75 118 Height mm 210 210 246 270 270 Approvals For bar systems with center-to-center spacing mm 60 60 60 60 60 For bar thickness mm 5/10 5/10 5/10 5/10 5/10 Part No. 1 9342.220 9342.250 9342.280 9342.224 9342.254 Accessories Laminated copper bars 302 266 Metric measurements for are exact, imperial measurements are rounded Rittal Catalog 33/Power distribution