RiLine60 fuse element Busbar systems Page 261 Connection system Page 266 Component adaptors Page 269 Material: Basis of test: Note: Technical information: − Polyamide (PA 6) – IEC/DIN EN 60 947-3 − For the use of fuse inserts Available at www.rittal-corp.com − Fire protection corresponding to DIN EN 60 269-3 to UL 94-V0 Configuration: (DIN VDE 0636-301). Detailed drawings: Reducing retaining springs for D01 − With integral visual fuse Available at www.rittal-corp.com Color: and 10 x 38 mm fuses. monitoring via flashing indicator − Chassis: RAL 7035 and operating status display. − Fuse holder: RAL 7001 Bus-mounting fuse base D-Switch (3-pole) Design Packs of Snap-on mounting D 011) Fuse inserts D 022) 10 x 38 mm1) Rated operating current 63 A Rated operating voltage 400 V~ Terminal for round conductors3) mm2 1.5 – 25 Min. voltage, indicator light 100 – 400 V~ Width mm 27 Height mm 226 For bar systems with center-to-center spacing mm 60 For bar thickness mm 5/10 Part No. 3 9340.950 1) When using D01 and 10 x 38 mm fuses, reducing retaining springs must be used. Use of D 01 fuses optionally possible with adaptor sleeve for D 02 base/plinths. 2) With Neozed adaptor sleeves for D 02. 3) Wire end ferrules should be used with fine wire conductors. Rittal Catalog 33/Power distribution Metric measurements for are exact, imperial measurements are rounded 281