TopTherm filter fan/exhaust Air Displacement: 1529 cfm (900 m3/h), with EC technology Part No. 3245.5001) 3245.6001) 3245.5101) EMC version – – Rated operating voltage V, Hz 230, 50/60 115, 50/60 W x H 13 x 13 (323 x 323) Dimensions inches (mm) D (T1) 1 (25) Max. installation depth inches (mm) D (T2) 5 (130.5) Air throughput with outlet filter 1 x 3243.200: 406 cfm (680 m3/h) 1 x 3243.060: 406 cfm (680 m3/h) 1 x 3243.200: 06 cfm (680 m3/h) including standard filter mat 2 x 3243.200: 483 cfm (820 m3/h) 2 x 3243.060: 483 cfm (820 m3/h) 2 x 3243.200: 483 cfm (820 m3/h) Diagonal fan EC motor Rated current 1.25 A 2.5 A Power consumption 170 W Pre-fuse 4 A 6 A Noise level 72 dB (A) Operating temperature range –22° F to +131° F (–30° C to +55° C) Storage temperature range –22° F to +158° F (–30° C to +70° C) Protection rating Standard IP 51 With additional fine filter mat IP 52 With hose-proof hood IP 56 Accessories PU Page SK outlet filter 1 3243.200 – 3243.200 485 SK outlet filter – EMC 1 – 3243.060 – 485 Spare filter mats 5 3173.100 3243.066 3173.100 483 Fine filter mats 5 3183.100 484 Hose-proof hood 1 3245.080 487 Blanking cover 1 3243.020 485 Enclosure internal thermostat 1 3110.000 476 Digital temp. display/thermostat 1 3114.200 475 Hygrostat 1 3118.000 476 Speed control/monitoring 1 3235.4402) 477 1) 0 – 10 V input and tacho signal output 2) On request. Special voltages available on request. We reserve the right to make technical modifications. 384 Metric measurements for are exact, imperial measurements are rounded Rittal Catalog 33/Climate control