Baying system Enclosure suite Baying clamp, vertical Packs of Part No. for TS/PS 6 8800.420 For mounting on the vertical enclosure sections. Material: Cast steel Surface finish: Zinc-plated Configuration: Assembly parts Baying connectors, external Material/surface finish Packs of Part No. for TS/TS Carbon steel, zinc-plated 6 8800.490 For mounting on the vertical enclosure sections. Simply position on the outside and screw-fasten Stainless steel Type 304 6 8700.000 either from the inside or outside. Configuration: Assembly parts Note on the transportation of bayed enclosures Individual enclosures may be safely transported For the enclosure The cable pull angle using the eyebolts included with the supply. combination with angular between the roof plate For symmetrical loads, the following maximum baying brackets, quick-fit and the cable has a permissible loads apply: baying clamps and significant influence for 45° cable pull angle 1079 lbf (4,800 N,) combination angles on the total permissible for 60° cable pull angle 1439 lbf (6,400 N), shown here, the load load. The cable pull angle for 90° cable pull angle 3057 lbf (13,600 N). capacity with a cable pull must not be less than angle of 60° is as follows: 45°, and where possible, Note: for the left-hand enclosure should be less than 60°. The eyebolts must be aligned in the direction of 1574 lbf (7,000 N), for the the cable pull. For larger baying combinations, we central enclosure 3147 lbf recommend the use of a transport base/plinth, (14,000 N), for the right see page 540. hand enclosure 1574 lbf (7,000 N). Rittal Catalog 33/System accessories Metric measurements for are exact, imperial measurements are rounded 575